User Manual of A90 Series Inverter (F04.19=0), the logic diagram is as shown in Fig. 5-3(d). (a) Wiring diagram of three-line control (F00.03=2) (b) Forward/reverse control logic (F04.19=0, F00.03=2) (c) Wiring diagram of two-line control (F00.03=3) (d) Forward/reverse running logic (F04.19=0, F00.03=3) Fig. 5-3 Three-line Control The three-line control logic of the A90 series inverter is consistent with the conventional electrical control. The keys and knob switches should be used correctly as shown in the schematic diagram. Otherwise, operation errors may be caused.
5.6 Common Process Parameters of Inverter 60 Function Function code Default Parameter description Unit Attribute code name setting F00.01 Drive control mode of motor 1 0: V/F control (VVF) 1: Speed sensorless vector control (SVC) 0 ○ F00.04 Options of main frequency source A 0: digital frequency setting F00.07 1: AI1 2: AI2 4: VP (keyboard potentiometer) 6: Percentage setting of main frequency communication 7: Direct setting of main frequency communication 0 ○ F00.07 Digital frequency setting 0.00 to maximum frequency F00.16 Hz 0.00 ● F00.14 Acceleration time 1 0.00~650.00 (F15.13=0) s 15.00 ●