User Manual of A90 Series Inverter 95 protection time F10 Communication function group F10.00 Local Modbus communication address 1-247; 0: broadcast address 1 ○ F10.01 Baud rate of Modbus communication 0: 4800 1: 9600 2: 19200 3: 38400 4: 57600 5: 115200 1 ○ F10.02 Modbus data format 0: 1-8-N-1 (1 start bit + 8 data bits + 1 stop bit) 1: 1-8-E-1 (1 start bit + 8 data bits + 1 even parity check bit + 1 stop bit) 2: 1-8-O-1 (1 start bit + 8 data bits + 1 odd parity check bit + 1 stop bit) 3: 1-8-N-2 (1 start bit + 8 data bits + 2 stop bits) 4: 1-8-E-2 (1 start bit + 8 data bits + 1 even parity check bit + 2 stop bits) 5:

1-8-O-2 (1 start bit + 8 data bits + 1 odd parity check bit + 2 stop bits) 0 ○ F10.03 Modbus communication timeout 0.0~60.0; 0.0: invalid (valid for master-slave mode) s 0.0 ● F10.04 Modbus response delay 1 - 20 ms 2 ● F10.05 Options of master-slave communication function 0: Invalid 1: valid 0 ○ F10.06 Master-slave options 0: slave 1: host (Modbus protocol broadcast transmission) 2: host (CANSinee protocol) 0 ○ F10.07 Data sent by host 0: output frequency 1: set frequency 2: output torque 1 ○