User Manual of A90 Series Inverter 98 F12.02 Parameter locking 0: do not lock 1: reference input not locked 2: all locked, except for this function code 0 ● F12.09 Load speed display coefficient 0.01~600.00 30.00 ● F12.10 UP/DOWN acceleration and deceleration rate 0.00: automatic rate 0.01~500.00 Hz/s 5.00 ○ F12.11 Options of UP/DOWN offset clearing 0: do not clear 1: clear in non-running state 2: clear when UP/DOWN invalid 0 ○ F12.12 Options of UP/DOWN power-down saving of offset 0: do not save 1: save (valid after the offset is modified) 1 ○ F12.13 Power meter resetting 0: do not clear 1: clear 0 ● F12.14 Restoration of default setting 0: No operation 1:

restoration of factory defaults (excluding the motor parameters, inverter parameters, manufacturer parameters, running and power-on time record) 0 ○ F12.15 Cumulative power-on time h 0~65,535 h XXX × F12.16 Cumulative power-on time min 0~59 min XXX × F12.17 Cumulative running time 0~65,535 h XXX × F12.18 Cumulative running time (min) 0~59 min XXX × F12.19 Rated power of inverter 0.40~650.00 kW Dependi ng on the motor type × F12.20 Rated voltage of inverter 60~690 V Dependi ng on the ×