Chapter 5 Basic Instructions Symbol: S : Specified device Bit Explanation: 1. The logical operation result prior to the application of the instruction OUT is output into the specified device. 2. The action of the coil contact: Example: 1. Contact B of X0.0 is loaded, contact A of X0.1 is connected in series, and the coil Y0.0 is driven. 2. When X0.0 is OFF, and X0.1 is ON, Y0.0 is ON. 5-7 Instruction code Operand Function OUT S Driving the coil Device DX DY X Y M SM S T C HC D L PR S ● ● ● ● ● ● ● ● ● ● ● ● OUT Operation Contact result Coil Contact A Contact B (normally open) (normally closed) False OFF OFF ON True ON ON OFF