Delta AH500 — 6.3.2 Explanation of Data Conversion Instructions

AH500 Programming Manual Destination value Maximum destination value =500 Minimum destination value D =30 0 Source value =3000 Example 2: 1. Suppose the value in S 1 is 500, the maximum source value in D0 is 3,000, the minimum source value in D1 is 200, the maximum destination value in D2 is 30, and the minimum destination value in D3 is 500. When X0.0 is ON, the instruction SCLP is executed, and the scale value is stored in D10. 2. The operation equation: D10=[(500–200)Ч(30–500)]ч(3,000–200)+500=449.64 449.64 is rounded off to the nearest whole digit, and becomes 450. 450 is stored in D10. 6-104 S1=500 Minimum Maximum source value =200 source va