Chapter 6 Applied Instructions 4. When the current value of C10 is within the range between the minimum value and the maximum value, M10~M13 are ON. Otherwise, M10~M13 are OFF. 5. Suppose the minimum value is larger than the maximum value. When the current value of C10 is less than the maximum value (C10 < 60), or when the current value of C10 is larger than the minimum value (C10 > 140), M12 is ON. Otherwise, M12 is OFF.
40 100 M10 M11 120 210 60 140 M12 M13 150 390 400 200 0 6-167 Minimum value Maximum value Current value of C10 Output D100=40 D101=100 40≦C10≦100 M10=ON D102=120 D103=210 120≦C10≦210 M11=ON D104=140 D105=170 140≦C10≦170 M12=ON D106=150 D107=390 150≦C10≦390 M13=ON Minimum value Maximum value Current value of C10 Output D100=40 D101=100 40≦C10≦100 M10=ON D102=120 D103=210 120≦C10≦210 M11=ON D104=140 D105=60 60≦C10≦140 M12=OFF D106=150 D107=390 150≦C10≦390 M13=ON