Delta AH500 — 6.20.2 Explanation of Other Instructions

Chapter 6 Applied Instructions API 1905 Symbol: D : Device from which the value is read Word Explanation: 1. The values in the devices specified by the value in D are read into E0~E31, and the value in D decreases by one. 2. The execution of the instruction involves thirty-four devices, and the last two devices are for system use. If the instruction is executed and the number of times the data is stored is n, which is the value in D , the data in D+34*(n-1)+1~D+34*(n-1)+32 is read into E0~E31, and the value in D becomes n-1. 3. The value which is stored last in the device specified by the value in D is read first. D The number of times the data is stored D +1 E0 E1 D +2 ...... ...... ......

...... D +32 E31 D +33 D +34 For system use +35 D E0 E1 +36 D D +37 E2 ...... Example: When X0.0 is ON, the value in D0 is set to 0, and the values in E0~E31 are transmitted to D1~D32. After the execution of FB0 is complete, the values in D1~D32 are read into D1~D32. 6-437 Instruction code Operand Function EPOP P D Reading the data into the index registers Device X Y M S T C HC D L SM SR E PR K 16# “$” DF D        Pulse instruction 16-bit instruction (3 steps) 32-bit instruction AH500 AH500 ─