Chapter 6 Applied Instructions 4. When the current value of C10 is between the minimum value and the maximum value, M10–M13 are ON. Otherwise, M10–M13 are OFF. 5. Suppose the minimum value is larger than the maximum value. When the current value of C10 is less than the maximum value (C10 < 60), or when the current value of C10 is larger than the minimum value (C10 > 140), M12 is ON. Otherwise, M12 is OFF.
6-193 Minimum value Maximum value Current value of C10 Output D100=40 D101=100 40≦C10≦100 M10=ON D102=120 D103=210 120≦C10≦210 M11=ON D104=140 D105=170 140≦C10≦170 M12=ON D106=150 D107=390 150≦C10≦390 M13=ON 6 _ Minimum value Maximum value Current value of C10 Output D100=40 D101=100 40≦C10≦100 M10=ON D102=120 D103=210 120≦C10≦210 M11=ON D104=140 D105=60 60≦C10≦140 M12=OFF D106=150 D107=390 150≦C10≦390 M13=ON