Delta Electronics — 6.19.2 Explanation of Communication Instructions

Chapter 6 Applied Instructions Example 5 The mode in D 2 is 4 (the data received starts with a specific character and you set the timeout value to 5–255 ms.) and you set the mode of sending and receiving data to 8-bit mode (SM106=ON). 1. The length for the data to be sent: D20=4. 2. The contents for the data to be sent: D100=16#0031, D101=16#0032, D102=16#0033, D103=16#0034. 3. Set D10=16#0004 (mode: 4), D11=16#3A0F (the starting character is 16#3A and set the time value to 16#0F, meaning 15ms). 4. Enable the contact X0.0. 5. The PLC sends 4 pieces of data. Sending data: PLC→external equipment 31 32 33 34 6.

The external equipment receives data from the PLC and then sends 7 consecutive words to the PLC with an interval of 1 ms between each sending. 6_ External equipment → PLC 30 3A 35 36 37 38 39 7. D200=6 (number of the data received), and the content of the received data: D201=16#003A, D202=16#0035, D203=16#0036, D204=16#0037, D205=16#0038, D206=16#0039. 8. SM100=ON: reception of data is complete. 9. To send more data, set the flag SM100 to OFF to start the operation again. NOTE: When the sending of data is complete, the receiving flag SM98 is ON and then the PLC is ready to receive data. When the PLC receives the starting character 16#3A, it starts receiving data.

The interval timeout between receiving each piece of data is set in D11. When the interval time exceeds the set timeout 16#0F (15 ms) and no data is coming in, SM100 is ON. 6-573