AS Series Programming Manual _6 1. Connect AS COU to VFD. Set D202=12000 initially. When M1 is ON, VFD starts to accelerate after receiving the clockwise running command, and runs clockwise at 120Hz. 2. Set D204=18000 initially. When M2 is ON, VFD starts to decelerate until it stops after receiving the counterclockwise running command, and runs counterclockwise at 180Hz. 3. When M3 is ON (at this time, the value in D206 is ignored), VFD decelerates to stop after receiving the stop command. 4. When M4 is ON, the instruction reads the values of H2100–H2104 of VFD and stores them in D220–224. 6-586