Delta Electronics — 6.22.2 Explanation of Ethernet Instructions

AS Series Programming Manual Explanation 1. This instruciton is available for PLC with FW V1.06.00. 2. See the operand name, use explanation and data type in the following table. 6-742 Operand Name Explanation Data type Remark Server Email server Server +0: Data length, unit: bytes (0 or 4; 0: no modification) Server +1~ Server +2: data (Data are placed from the lower 8 bits.) For example: 192.168.0.1, D0 = 16#0004, D1= 16#0001, D2= 16#C0A8; WORD[N] Refer to Server +0 for address occupation. 3 consecutive words at most can be occupied.

Up to 15 words can be used in one string; every section in one string can contain 1-3 words, and use a dot “.” to separate each string, for example 192.168.0.1 String Port Communication port Range: 1~65535, 0: no modification WORD LMail Local email address LMail +0: data length, unit: bytes (range: 0~63, 0: no modification.) LMail +1~ LMail +32: data (Data are placed from the lower 8 bits.) For example: ex@deltaww.com D0 = 16#000E, D1 = 16#7865, D2 = 16#6440, D3 = 16#6C65, D4 = 16#6174, D5 = 16#7777, D6 = 16#2E63, D7 = 16#6D6F WORD[N] Refer to LMail +0 for address occupation. 33 consecutive words at most can be occupied.

Up to 63 words can be used in one string String Sub Email subject Sub +0: data length, unit: bytes (range: 0~31, 0: no modification.) Sub +1~ Sub +16: data content (Data are placed from the lower 8 bits.) For example: Sub 0 = 16#0003, D1 = 16#7553, D2 = 16#0062 WORD[N] Refer to Sub +0 for address occupation. 17 consecutive words at most can be occupied. Up to 31 words can be used in one string String Verify Enable/ disable verification 0: no modification, 1: Disable verification, 2: Enable verification WORD User User name User +0: data length, unit: bytes (range: WORD[N] Refer to User +0 6 _