Delta CFP2000 — 7-2 Magnetic Contactor / Air Circuit Breaker and Non-fuse Circuit Breaker

Chapter 7 Optional Accessories  CFP2000 7-2 Magnetic Contactor / Air Circuit Breaker and Non-fuse Circuit Breaker Magnetic Contactor (MC) and Air Circuit Breaker (ACB) It is recommended the surrounding temperature for MC should be ≥ 60°C and that for ACB should be ≥ 50°C. In the meanwhile, consider temperature derating for components with ON/OFF switch in accordance with the ambient temperature of the on-site distribution panel.

Table 7-4 7-8 Frame Model Light duty output Light duty input MC/ACB selection current [A] current [A] [A] A VFD007FP4EA-41/-52/-52S 3 3 7 VFD015FP4EA-41/-52/-52S 4.2 4.2 7 VFD022FP4EA-41/-52/-52S 5.5 5.5 9 VFD037FP4EA-41/-52/-52S 8.5 8.5 18 VFD040FP4EA-41/-52/-52S 10.5 10.5 18 VFD055FP4EA-41/-52/-52S 13 13 22 VFD075FP4EA-41/-52/-52S 18 18 32 B VFD110FP4EA-41/-52/-52S 24 24 40 VFD150FP4EA-41/-52/-52S 32 32 50 VFD185FP4EA-41/-52/-52S 38 38 65 C VFD220FP4EA-41/-52/-52S 45 45 75 VFD300FP4EA-41/-52/-52S 60 60 105 VFD370FP4EA-41/-52/-52S 73 73 130 D0 VFD450FP4EA-41/-52/-52S 91 91 150 VFD550FP4EA-41/-52/-52S 110 110 185 D VFD750FP4EA-41/-52/-52S 150 150 265 VFD900FP4EA-41/-52/-52S 180 180 330