Daikin BRC1H61W/BRC1H61K — 00_CV_EM19A034_IM.indd

INFORMATION When the value for a parameter is “- -”, this means that when the timers expires, nothing changes for that parameter and the current active value is kept. Window contact logic 38 Parameter Description Possible values Default value Reset Heat SP 22 “Default Reset Setting” heating setpoint See indoor unit’s setpoint range and setpoint range limitation, “--” “22°C” Window contact B1 Key card contact B2 Time Action Contact closed (window open) Contact closed (key card IN) — • Normal indoor unit operation. • The unit returns to the previous state before opening the contact. Contact open (window open) Contact closed (key card IN) — Unit operation is forced off:

• No delay and reset timer functionality. • No Setback functionality. • Not possible to turn on/of f the unit with the controller’s ON/OFF button.