2. Programming Concepts 2-13 OFF STOP RUN Special ES2 SA2 Latch Function SS2 SX2 Attrib. Default M EX2 SE -ed ON RUN STOP M1012* 100ms clock pulse, 50ms ON / 50ms OFF ○ ○ ○ ○ OFF - - R NO OFF M1013* 1s clock pulse, 0.5s ON / 0.5s OFF ○ ○ ○ ○ OFF - - R NO OFF M1014* 1 min clock pulse, 30s ON / 30s OFF ○ ○ ○ ○ OFF - - R NO OFF M1015* Enable high-speed timer ○ ○ ○ ○ OFF - - R/W NO OFF M1016* Indicate Year display mode of RTC. ○ ○ ○ ○ OFF - - R/W NO OFF M1017* ±30 seconds correction on real time clock ○ ○ ○ ○ OFF - - R/W NO OFF M1018 Flag for Radian/Degree, ON for degree ○ ○ ○ ○ OFF - - R/W NO OFF M1019* If the PLC detects the external 24V voltage is unstable; OFF:
the PLC runs after the power is stabilized, ON: the error LED keeps flashing ○ ○ ○ ○ OFF - - R/W NO OFF M1020 Zero flag ○ ○ ○ ○ OFF - - R NO OFF M1021 Borrow flag ○ ○ ○ ○ OFF - - R NO OFF M1022 Carry flag ○ ○ ○ ○ OFF - - R NO OFF M1024 COM1 monitor request ○ ○ ○ ○ OFF - - R/W NO OFF M1025* Indicate incorrect request for communication ○ ○ ○ ○ OFF - - R NO OFF M1026 RAMP mode selection ○ ○ ○ ○ OFF - - R/W NO OFF M1027 PR output mode selection (8/16 bytes) ○ ○ ○ ○ OFF - - R/W NO OFF M1028 Switch T64~T126 timer resulotion (10ms/100ms). ON =10ms ○ ○ ○ ○ OFF - - R/W NO OFF M1029* CH0 (Y0, Y1) pulse output execution completed.
○ ○ ○ ○ OFF - - R NO OFF M1030* Pulse output Y1 execution completed ○ ○ ○ ○ OFF - - R NO OFF M1031* Clear all non-latched memory ○ ○ ○ ○ OFF - - R/W NO OFF M1032* Clear all latched memory ○ ○ ○ ○ OFF - - R/W NO OFF M1033* Output state latched at STOP ○ ○ ○ ○ OFF - - R/W NO OFF M1034* Disable all Y outputs ○ ○ ○ ○ OFF - - R/W NO OFF M1035* Enable X7 input point as RUN/STOP switch ○ ○ ○ ○ - - - R/W YES OFF M1037* Enable 8-sets SPD function (Has to be used with D1037) (SE does not support this function.) ╳ ╳ ○ ○ OFF OFF OFF R/W NO OFF M1038 Switch T200~T255 timer resulotion (10ms/1ms).
ON = 1ms ○ ○ ○ ○ OFF - - R/W NO OFF M1039* Fix scan time ○ ○ ○ ○ OFF - - R/W NO OFF M1040 Disable step transition ○ ○ ○ ○ OFF - - R/W NO OFF M1041 Step transition start ○ ○ ○ ○ OFF - OFF R/W NO OFF M1042 Enable pulse operation ○ ○ ○ ○ OFF - - R/W NO OFF M1043 Zero return completed ○ ○ ○ ○ OFF - OFF R/W NO OFF M1044 Zero point condition ○ ○ ○ ○ OFF - OFF R/W NO OFF M1045 Disable “all output reset” function ○ ○ ○ ○ OFF - - R/W NO OFF M1046 Indicate STL status ○ ○ ○ ○ OFF - - R NO OFF M1047 Enable STL monitoring ○ ○ ○ ○ OFF - - R/W NO OFF M1048 Indicate alarm status ○ ○ ○ ○ OFF - - R NO OFF M1049 Enable alarm monitoring ○ ○ ○ ○ OFF - - R/W NO OFF M1050 Disable interruption I000 / I001 ○ ○ ○ ○ OFF - - R/W NO OFF M1051 Disable interruption I100 / I101 ○ ○ ○ ○ OFF - - R/W NO OFF M1052 Disable interruption I200 / I201 ○ ○ ○ ○ OFF - - R/W NO OFF M1053 Disable interruption I300 / I301 ○ ○ ○ ○ OFF - - R/W NO OFF M1054 Disable interruption I400 / I401 ○ ○ ○ ○ OFF - - R/W NO OFF M1055 Disable interruption I500 / I501 ○ ○ ○ ○ OFF - - R/W NO OFF M1056 Disable interruption I600~I699 ○ ○ ○ ○ OFF - - R/W NO OFF M1057 Disable interruption I700~I799 Disable interruption I805~I899 (V2.00 and above are supported.) ○ ○ ○ ○ OFF - - R/W NO OFF M1058 COM3 monitor request ○ ╳ ○ ○ OFF - - R/W NO OFF M1059 Disable high-speed counter interruptions I010~I080 ○ ○ ○ ○ OFF - - R/W NO OFF M1060 System error message 1 ○ ○ ○ ○ OFF - - R NO OFF M1061 System error message 2 ○ ○ ○ ○ OFF - - R NO OFF