Delta DVP-ES3 — 2.4.1 General Specifications

Chapter 2 Specifications and System Configuratio n 2_  DVP06XA-E2 Electrical specifications Things to note when connecting the module to a CPU PLC module: 1. Up to 8 modules can be connected to a CPU PLC module. 2. The connected module is numbered automatically from 0 (nearest to the CPU PLC module) to 7 (furthest away from the CPU PLC module). 3. The connected modules do NOT take up any digital I/O points. A/D Functional specifications 2-18 Digital/analog module Voltage output Current output An analog circuit is isolated from a digital circuit by a digital integrated circuit/an optocoupler, but the analog channels are not isolated from one another.

Isolation between a digital circuit and a ground: 500 VDC Isolation between an analog circuit and a ground: 500 VDC Isolation between an analog circuit and a digital circuit: 500 VDC Isolation between the 24 VDC and a ground: 500 VDC Isolation Module name DVP06XA-E2 Number of inputs/outputs Inputs: four; Outputs:

two Analog-to-digital Voltage input/Current input; Voltage output/Current output; conversion Supply voltage 24 VDC (20.4 VDC–28.8 VDC) (-15% to +20%) Connector type Removable terminal block (distance to the terminal is 5 mm) Conversion time 400 μs /channel Weight 213 g Voltage input Current input Analog input channel 4 channels Rated input range ±10V ±5V ±20 mA 0 ~ 20 mA 4 ~ 20 mA Digital conversion range ±32,000 ±32,000 ±32,000 0 ~ 32,000 0 ~ 32,000 Hardware input limit*1 ±10.12V ±5.06V ±20.24 mA -0.24~20.24 mA 3.81 ~ 20.19 mA Digital conversion limit*2 ±32,384 ±32,384 ±32,384 -384 ~+32,384 -384 ~ +32,384 Hardware resolution 14-bit 14-bit 14-bit 13-bit 13-bit Input impedance ≧1M Ω 250 Ω Absolute input range*3 ±15 V ±32 mA Digital data format 16-bit two’s complement number Average function Yes, CR#8 ~ CR#11, setting range:

K1 ~ K100 Self-diagnosis function Detecting if exceeding upper and lower limts or channel disconnection 25° C/77° F: The allowed error range is ±0.5% of full scale. 0° C to 55° C/-32° F to 131° F: The allowed error range is ±1% of full scale. Overall Accuracy