DVP-ES3 Series Programming Manual _6 6-204 Setting Operand Data type Function Description range status condition. If the present error is less than the absolute value of ERR DBW, _ and meets the cross status condition, the present error is counted as 0, and the PLC applies the PID algorithm ; otherwise the present error is brought into the PID algorithm according to the normal processing. MV MAX _ REAL Maximum output value Range of single- precision floating- point numbers Suppose MV MAX is _ set to 1,000. When MV is larger than 1,000, 1,000 is the output. The value in MV MAX _ should be larger than that in MV MIN. _ Otherwise, the maximum MV and the minimum MV are reversed.
MV MIN _ REAL Minimum output value Range of single- precision floating- point numbers Suppose MV MIN is _ set to -1,000. When the MV is less than -1,000, -1,000 is the output. MOUT REAL MV Range of single- precision When set to PID Manual, the MV value is output as the setting