Delta DVP-ES3 — 6.8.2 Explanation of Miscellaneous Instructions

Chapter 6 Applied Instructions Step 2 : When the K P is 40, there is overreaction. When the K P is 20, the reaction curve of PV is close to SV, and there is no overreaction. However, due to the fast start-up, the transient output value (MV) is big. Neither 40 nor 20 is a suitable value. When the K P is 10, the reaction curve of PV approaches SV smoothly. When K P is 5, the reaction is too slow. Therefore, K P = 10 is the best choice. Step 3 : After setting K P to 10, increase K I . For example, K I is successively set to 1, 2, 4, and 8. K I should not be larger than K P . Then, increase K D . For example, successively set K D to 0.01, 0.05, 0.1, and 0.2.

K D should not be larger than ten percent of K P . Finally, the relation between PV and SV is shown in the following diagram. 1.5 PV=SV 1 0.5 K =10,K =8,K =0.2 P I D 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 Time (sec) Note: This example is only for reference. You must tune the parameters properly according to the actual condition of the control system. 6_ 6-211