Delta DVP-ES3 — 6.13.2 Explanation of Data Processing Instructions

Chapter 6 Applied Instructions n 6_ Additional remarks 1. If S 1 + n -1 or D +4 exceeds the device range, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 2. For 16-bit instructions, if the value in n is not between 1 – 256, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#200B. 3. For 32-bit instructions, if the value in n is not between 1 – 128, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#200B. 4. For 16-bit instructions, if you declare the operand D in ISPSoft, the data type is ARRAY [5] of WORD/INT. 5.

For 32-bit instructions, if you declare the operand D in ISPSoft, the data type is ARRAY [5] of DWORD/DINT. 6-345 Compared Data Result D S1 Value Value Description data number D10 88 S2 D0=100 0 D50 4 Number of equal values D11 100 1 Equal D51 1 Data number of the first equal value D12 110 2 D52 8 Data number of the last equal value D13 150 3 D53 7 Data number of the minimum value D14 100 4 Equal Data number of the D54 9 maximum value 9 Data number of the maximum value D15 300 5 D16 100 6 Equal D17 5 7 Minimum D18 100 8 Equal D19 500 9 Maximum