Delta DVP-ES3 — 6.17.2 Explanation of Real-time Clock Instructions

DVP-ES3 Series Programming Manual 2. If the difference is a negative, SM601 is ON. 5 ( Hour ) 20 ( Minute ) 30 ( Second ) 19 ( ) Hour 11 ( ) Minute 15 ( ) Second 10 ( ) Hour 9 ( ) Minute 15 ( ) Second - 5 hour 20 minute 30 second 19 hour 11 minute 15 second 10 hour 9 minute 15 second Additional remarks 1. If the value in S 1 or S 2 exceeds the range, an operation error occurs, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 2. If S 1 +2, S 2 +2, or D +2 exceeds the device range, an operation error occurs, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 3.

If you declare the operand S 1 in ISPSoft, the data type is ARRAY [3] of WORD/INT. _6 4. If you declare the operand S 2 in ISPSoft, the data type is ARRAY [3] of WORD/INT. 5. If you declare the operand D in ISPSoft, the data type is ARRAY [3] of WORD/INT. 6-484