Delta DVP — 12.3 Communication between PLC and Delta VFD-V Series AC Motor Drive

12. Communication Design Examples M1140 C0 counts once when data receiving error occurs. M1141 Reset the flag M1140 C0 counts once when parameter error occurs. Reset the flag M1141 Program Description: z Initialize PLC RS-485 communication port and set the communication format as MODBUS RTU, 19200, 8, N, 2. The RS-485 communication format of AC motor drive should be the same with PLC. z Reset D0 and D1 when PLC is powered up so as to ensure the drive is in the Stop status z When X0 is activated, the drive will run forward (D0 = H12) in 30Hz (D1 = 3000). z When X1 is activated, the drive will run in reverse (D0 = H22) in 20Hz (D1 = K2000) z When X2 is activated, the drive will stop.

(D0 = H1, D1 = 0) z There are only 4 situations for MODBUS communication: flag M1127 for normal communication and M1129, M1140, M1141 for communication errors. Counter C0 counts once when any of the 4 flags is ON. Therefore, the program assures the communication reliability by monitoring the On/Off status of the 4 flags and performs 2 MODBUS instructions in order by the value in counter C0. z The master frequency and output frequency stored in D1050 and D1051 will be sent to D2 and D3. z Once PLC starts running, the read/write actions for AC motor drive will be performed repeatedly according to [LD=] instructions. DVP-PLC Application Examples 12-13 CNT C0 K10 RST M1140 CNT C0 K10 RST M1141