2 Functions of Devices in DVP-PLC (X5 is the external interruption input), and C245 is used, the function is enabled, but the high-speed counting value will not be cleared. Function Group Auto-mapping Function Number M1182 ~ M1183, D9800 ~ D9879, D9900~D9979 1. The default value of M1182 is ON. When M1182 is OFF, the auto-mapping function is enabled. The analog-to-digital values/digital-to-analog values correspond to D9800~D9879. If the first left-side module connected to EH3-L/SV2 is a communication module, the analog-to-digital values/digital-to-analog values correspond to D9810~. For example, if the modules be assigned to CH1~CH4 in the third left-side module 04DA-SL.
connected to SV2 from left to right are 04DA-SL, EN01-SL, and 04AD-SL, and M1182 is OFF, D9820~D9823 will Note: The default value of M1182 in SV2 version 1.0 is OFF. If users want to disable the auto-mapping function, they have to set M1182 to ON. 2. The default value of M1183 is ON. When M1183 is OFF, the auto-mapping function is enabled. The analog-to-digital values/digital-to-analog values correspond to D9900~D9979.
For example, if the modules connected to SV2 from left to right are 04DA-S, 04DA-S, and 06XA-S, and M1182 is OFF, D9900~D9903 will be assigned to CH1~CH4 in the first right-side module 04DA-S, D9910~D9913 will be assigned to CH1~CH4 in the second right-side module 04DA-S, and D9920~D9925 will be assigned to CH1~CH6 in the third module 06XA-S.
DVP-PLC Application Manual 2-119 04DA-SL EN01-SL 04AD-SL SV2 Third left-side module Second left-side module First left-side module D9820 X D9800 CH1 AIO conversion value D9821 X D9801 CH2 AIO conversion value D9822 X D9802 CH3 AIO conversion value D9823 X D9803 CH4 AIO conversion value SV2 04DA-S 04AD-S 06XA-S First module Second module Third module CH1 AIO conversion value D9900 D9910 D9920 CH2 AIO conversion value D9901 D9911 D9921 CH3 AIO conversion value D9902 D9912 D9922 CH4 AIO conversion value D9903 D9913 D9923 CH5 AIO conversion value X X D9924 CH6 AIO conversion value X X D9925