Mitsubishi — 2.11 Functions of Special Auxiliary Relays and Special Registers

2 Functions of Devices in DVP-PLC Function Group Latched Area Number D1200 ~ D1219 Contents: 1. The latched area for EH2/SV/EH3/SV2 and SA/SX/SC is from the start address No. to the end address No. 2. See the tables in Chapter 2.1 for more details. Function Group Set On/Off of Input Point X on MPU Number M1304 Contents: 1. For SS/ES/EX, when M1304 = On, the X input points (X0 ~ X17) on MPU can be set On/Off by peripheral devices, e.g. WPLSoft or DVP-HPP. However, the LED indicators will not respond to the setup. 2. For SA/SX/SC, when M1304 = On, peripheral devices, e.g. WPLSoft or DVP-HPP, can set On/Off of X0 ~ X17 on the MPU, but the LED indicators will not respond to it. 3.

For EH2/SV/EH3/SV2, when M1304 = On, peripheral devices, e.g. WPLSoft or DVP-HPP, can set On/Off of X input points on the MPU, but the LED indicators will not respond to it. Function Group High-speed Output Pulse Stop Mode Number M1310 ~ M1311, M1334 ~ M1335, D1166 ~ D1167, D1343 ~ D1353 Contents: 1. Special D and special M for high-speed pulse output stop mode: (SC_V1.4 and versions above are with an additional mode 3) 2. How do Y10 pulse output stop modes work: a) Using Y10 pulse output  Mode 1 – Planned deceleration Applicable to: DDRVI and DDRVA instructions Criteria for executing planned deceleration: Shut down the criteria contact for pulse output instruction and turn “Off” M1334.

The time from executing planned deceleration to the end of pulse output: The time set in D1343 (for acceleration/deceleration) DVP-PLC Application Manual 2-121 Device No. Function M1334 Select stop mode for Y10 pulse M1335 Select stop mode for Y11 pulse M1310 Immediately stop Y10 pulse output M1311 Immediately stop Y11 pulse output D1166 X10 rising-edge/falling-edge counting mode switch D1167 X11 rising-edge/falling-edge counting mode switch D1343 Acceleration/deceleration time for Y10 pulse output D1353 Acceleration/deceleration time for Y11 pulse output