2 Functions of Devices in DVP-PLC b) Example 2: PLC LINK with M1353 and I170 I170 With I170, the processing of data in PLC LINK will not be done at END, but at the enabling of I170 immediately after the receiving of data is completed If the reaction speed of the RS-485 IC direction control signal pin of the Slave is slow, it is suggested that you do not enable I170. You can set up D1399 (starting Slave ID designated by PLC LINK), and the ID# of the next 15 Slaves have to be in sequence. For example, when D1399 is set as K20, the Master PLC will detect Slave ID# 20 ~ 35.
DVP-PLC Application Manual 2-136 M1002 SET M1353 MOV K17 D1121 MOV H86 D1120 SET M1120 MOV K2000 D1480 MOV K3000 D1496 MOV K300 D1129 MOV K48 D1434 MOV K48 D1450 X1 M1350 M1351 FEND IRET END END SET M1353 MOV K17 D1121 MOV H86 D1120 SET M1120 MOV K2000 D1480 MOV K3000 D1496 MOV K300 D1129 MOV K48 D1434 MOV K48 D1450