Mitsubishi — Chapter 6 Application Instructions API 00-49

6 Application Instructions API 00-49 3. When X10 = Off→On, this instruction will encode 2 3 bits (b0 ~ b7) in D10 and stores the result in the lower 3 bits (b2 ~ b0) of D20. b15 ~ b3 that have not been used in D20 will all become 0. b8 ~ b15 of D10 are invalid data. 4. After the execution of this instruction is completed and X10 turns to Off, the content in D remains unchanged. X0 Invalid data b0 6 5 4 3 2 1 0 b15 7 D10 all be 0 b15 b0 D20 DVP-PLC Application Manual 6-66 ENCOP D10 D20 K3 0 1 0 1 0 1 0 1 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1