8 Application Instructions API 100-149 API 123 Operands: S 1 : Dividend S 2 : Divisor D : Quotient and remainder Explanations: 1. See the specifications of each model for their range of use. 2. Flags: M1020 (zero flag); M1021 (borrow flag); M1022 (carry flag) 3. S 1  S 2  D . The floating point value in the register designated by S 1 is divided by the floating point value in the register assigned by S 2 and the result is stored in the register designated by D . The division is conducted in binary floating point system. 4. If S 1 or S 2 is an designated constant K or H, the instruction will convert the constant into a binary floating point value before the operation. 5.

If S 2 = 0, operation error will occur, the instruction will not be executed, M1067, M1068 = On and D1067 will recorded the error code H’0E19. 6. If the absolute value of the result > maximum floating point available, the carry flag M1022 = On. 7. If the absolute value of the result < minimum floating point available, the borrow flag M1021 = On. 8. If the result = 0, the zero flag M1020 = On. Program Example 1: When X1 = On, binary floating point (D1, D0) ч binary floating point (D11, D10) and the quotient is stored in (D21, D20). X1 Program Example 2:

When X2 = On, binary floating point (D1, D0) ч K1234 (automatically converted into binary floating point ) and the result is stored in (D11, D10). X2 Remarks: For floating point operations, see “5.3 Handling of Numeric Values”. DVP-PLC Application Manual 8-38 Mnemonic Operands Function D EDIV P Floating Point Division Type OP Bit Devices Word Devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F DEDIV, DEDIVP: 13 steps S 1 * * * S 2 * * * D * PULSE 16-bit 32-bit EH3 ES EX SS SA SX SC EH SV EH3 SV2 EH3 ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV SV2 SV2 DEDIV D0 D10 D20 2 DEDIV D0 K1234 D10