9 Application Instructions API 150-199 l) For SC series MPU, due to that this instruction does not compare between the number of output pulses, the DOG input (from Off to On) will therefore become the trigger of acceleration converting to deceleration. The “On” time of DOG has to be longer than 10us; otherwise the signal may be regarded as useless interference. m) For SC series MPU, when the execution of the instrucion enters the deceleration segment and the output frequency reaches creep speed (end frequency), the output will stop when DOG goes from On to Off.
n) For SC series MPU, the current accumulated number of pulses of Y10 is stored in D1348 and D1349 and that of Y11 is stored in D1350 and D1351. Then the program operates from STOP to RUN or from RUN to STOP, the contents will not be cleared to 0. o) For SC series MPU, M1102 = On indicates the end of Y10 pulse output; M1103 = On indicates the end of Y11 p) For SC series MPU, after the instruction is executed, all parameters cannot be modified unless the execution pulse output. of the instruction stops. q) For SC series MPU, when the execution of the stops, all outputs will stop immediately no matter what type of the output it is. DVP-PLC Application Manual 9-48