2 Functions of Devices in DVP-PLC DVP-PLC Application Manual 2-43 ES SA Off STOP RUN Special EH2 EH3 Function EX SX    Attribute Latched Default M SV SV2 SS SC On RUN STOP M1154* Enabling the deceleration function of adjustable pulse output Y0 ╳ ○ ╳ ╳ Off - - R/W NO Off PWD bandwidth detection duty-off/duty-on ╳ ╳ ○ ○ Off Off - R/W NO Off M1155 The instruction DCIMA or DCIMR enables the automatic acceleration/deceleration.

╳ ╳ ○ ○ Off - - R/W NO Off M1156* Enabling X0 interruption, immediate deceleration and stopping CH0 high-speed output (When M1156 is enabled and M1538 = On, clear M1156 to send the remaining output pulses.) ╳ ╳ ○ ○ Off Off - R/W NO Off M1157* Enabling X1 interruption, immediate deceleration and stopping CH1 high-speed output ╳ ╳ ○ ○ Off Off - R/W NO Off M1158* Enabling X2 interruption, immediate deceleration and stopping CH2 high-speed output ╳ ╳ ○ ○ Off Off - R/W NO Off M1159* Enabling X3 interruption, immediate deceleration and stopping CH3 high-speed output ╳ ╳ ○ ○ Off Off - R/W NO Off M1160 SA/SX:

X4, X5 bandwidth detection flag (Not available in SX V3.0 and above) ╳ ○ ╳ ╳ Off Off Off R/W NO Off M1161 8-bit mode On: in 8-bit mode ○ ○ ○ ○ Off - - R/W NO Off M1162 Switching between decimal integer and binary floating point for SCLP instruction On: binary floating point; Off: decimal integer ○ ○ ○ ○ Off - - R/W NO Off M1163 Read/write memory card according to value in D1063 (automatically Off once the execution is completed) ╳ ╳ ○ ○ Off - - R/W NO Off M1164 Read/write internal Flash ROM according to value in D1064 (automatically Off once the execution is completed) ╳ ╳ ○ ○ Off - - R/W NO Off M1165 When On, the program and password on flash will be copied to the PLC when PLC is powered.

(Not available in EH2) ╳ ╳ ○ ╳ - - - R/W YES Off M1166 When On, the recipe on flash will be copied to the PLC when PLC is powered. (Not available in EH2) ╳ ╳ ○ ╳ - - - R/W YES Off M1167 16-bit mode for HKY input ╳ ○ ○ ○ Off - - R/W NO Off M1168 Designating work mode of SMOV ╳ ○ ○ ○ Off - - R/W NO Off M1169 Selecting PWD modes ╳ ╳ ○ ○ Off - - R/W NO Off M1170* Enabling single step execution ╳ ╳ ○ ○ Off - - R/W NO Off M1171* Single step execution ╳ ╳ ○ ○ Off - - R/W NO Off M1172* Switch for 2-phase pulse output On: switch on (Not available in SX V3.0 and above) ╳ ○ ╳ ╳ Off Off Off R/W NO Off M1173* On:

continuous output (Not available in SX V3.0 and above) ╳ ○ ╳ ╳ Off - - R/W NO Off M1174* The number of output pulses reaches the target (Not available in SX V3.0 and above) ╳ ○ ╳ ╳ Off Off - R/W NO Off M1175 Losing PLC parameter data (not available in EH2) ╳ ╳ ○ ○ - - - R YES Off M1176 Losing the data in PLC program (not available in EH2) ╳ ╳ ○ ○ - - - R YES Off M1177 The instruction DABSR is used with a servo drive. ╳ ╳ ╳ ○ Off - - R/W NO Off M1178* Enabling VR0 rotary switch ╳ ○ ○ ○ Off - - R/W NO Off M1179* Enabling VR1 rotary switch ╳ ○ ○ ○ Off - - R/W NO Off