Mitsubishi — 11.7 Appendix G: Using Ethernet Communication

11 Appendix 11.7 Appendix G: Using Ethernet Communication Specifications for an Ethernet interface: The specifications for a DVP series Ethernet port and the functions of a DVP series Ethernet port are listed below. Ethernet functions: Station Addresses of Ethernet Modules and Control Registers Station Addresses of Ethernet Modules Example 1. Suppose a DVP-SV series PLC is connected to three left-side communication modules. DVP-SE Series PLC (Ethernet PLC) In order to control and monitor Ethernet communication, users can read the data in the control registers listed below by means of the instruction FROM, and write data into the control registers listed below by means of the instruction TO.

(Please refer to the explanation of API 78 and that of API 79 in chapter 3 for more information about FROM/TO.) [Note] Please refer to DVPEN01-SL Manual for more information about control registers.

DVP-PLC Application Manual 11-14 Item Specifications Interface RJ-45 with Auto MDI/MDIX Number of ports 1 Port Transmission method IEEE802.3, IEEE802.3u Transmission cable Category 5e Transmission rate 10/100 Mbps Auto-Defect Protocol ICMP, IP, TCP, UDP, DHCP, SMTP, NTP, MODBUS TCP Function Built-in Ethernet port in a DVP-SE series PLC DVPEN01-SL DVP-FEN01 (Function card for a DVP-EH3 series PLC) MODBUS/TCP Master & Slave Master & Slave Master & Slave Number of servers 16 16 4 Number of clients 8 16 4 Number of data exchanged 8 24 8 RTU mapping - 4 - E-mail - 4 - SNMP - 2 - IP filter 4 8 4 Model name Built-in Ethernet port in a DVP-SE series PLC DVPEN01-SL DVP-FEN01 (Function card for a DVP-EH3 series PLC) FROM/TO station K108 See example 1.

K108 address PLC/Module name DVPEN01-SL DVPCOPM-SL DVPEN01-SL DVP28SV11R FROM/TO station K102 K101 K100 -- address CR number Attribute Register name Description HW LW #12 #0 - Reserved #13 R/W Enabling the data exchange Users can set CR#13 to “sending the data” or “not sending the data”.