User Manual EM303B General Purpose Inverter FE-06 and FE-07 set the output waveform of relay and multi-function terminal. For instance: If setting FE-07 ones place=0(Positive logic), FE-06 ones place selects pulse signal or voltage signal, as shown in Figure 7-36. If setting FE-07 ones place=1 (Negative logic), FE-06 ones place selects pulse signal or voltage signal, as shown in Figure 7-37. Pulse time is set by FE-10. 8.15.6 Virtual Terminal Function Terminal control selects actual terminal, analog communication to control on/off of terminal, input is set as enabled or disabled, or output is forced output or forced to be off. See the Appendix for communication format and data.

8.15.7 Relay and Multi-function Terminal Output Time Control 160 Tens place: Y2 output logic options 0: Positive logic 1: Negative logic Hundreds place: R1 output logic options 0: Positive logic 1: Negative logic Voltage V Control Program Input Terminal Output Voltage Terminal Output Pulse Pulse Time T Wideband Voltage V Control Program Input Terminal Output Voltage Terminal Output Pulse Pulse Time T Wideband Figure7-36 Output Waveform Selection Figure7-37 Output Waveform Selection No. Function Range Unit Default Type Virtual Terminal Options Ones place: Terminals Y1/Y2/R1 0: Actual output terminal 1: Virtual output terminal Tens place: Multi-function Input Terminal Xi 0:

Actual output terminal 1: Virtual output terminal Hundreds place: Numeric terminal VS/IS/VF/IF 0: Actual output terminal 1: Virtual output terminal 000 〇 FE-08 No. Function Range Unit Default Type