User Manual EM303B General Purpose Inverter Terminal Y1 will be taken as an example to describe the function of terminal delay time. If setting FE-07 ones place=1, FE-06 ones place selects pulse signal or voltage signal, as shown in Figure 7-38. Control Program Input Terminal Output Voltage Terminal Output Pulse Delay Time Wideband Figure 7-38 Terminal Output Delay Time 8.15.8 Distinguish Similar Faults In order to distinguish the faults clearly which are in similar logic or share the same fault display code, the specific fault type can be confirmed by reviewing the setting value of FE-20, FE-21, and FE-22.

161 FE-09 Terminal Y1 Delay Time 0.0~600.0 S 0.0 〇 FE-10 Terminal Y1 Pulse Width 0.0~600.0 S 5.0 〇 FE-11 Terminal Y2 Delay Time 0.0~600.0 S 0.0 〇 FE-12 Terminal Y2 Pulse Width 0.0~600.0 S 5.0 〇 FE-13 Terminal R1 Delay Time 0.0~600.0 S 0.0 〇 FE-14 Terminal R1 Pulse Width 0.0~600.0 S 5.0 〇 Voltage V Time No. Function Range Unit Default Type SC and EMC Faults Display 0: SCDrive failure 1: EMCEnvironment failure 0 X FE-20 SlU andSOFT Faults Display 0: SlU Stable undervoltage fault 1: SOFT Soft-start fault 0 X FE-21 SCI/SPI/PIDFaults Display 0: SCIFault 1: SPIFault 2:PID feedback loss fault 0 X FE-22 FE-23 Not Used ~ FE-31