3 Electrical Installation „ Control Circuit Terminals NOTICE! The terminals HC, H1, H2 are used for the Safe Disable function which cuts the output voltage in less than 1 ms if at least one of the inputs H1 or H2 is opened. It is designed in accordance with the EN954-1, safety category 3 and EN61508, SIL2. It and can be utilized to perform a safe stop as defined by the EN60204-1, stop category 0. Do not remove the wire link between HC, H1, or H2 unless the Safe Disable function is used. 14 I67E-EN V1000 Quick Start Guide Type No.
Terminal Name (Signal) Function (Signal Level), Default Setting Multi- Function Digital Inputs S1 to S6 Multi-function digital input 1 to 6 Photocoupler inputs, 24 Vdc, 8 mA Note: Drive preset to sinking mode (NPN). When using source mode, set DIP switch S3 to “SOURCE” and use an external 24 Vdc (±10%) power supply. SC Multi-function input common Sequence common Multi- Function Analog/ Pulse Inputs RP Pulse train input Response frequency: 0.5 to 32 kHz, Duty: 30 to 70%, High: 3.5 to 13.2 V, Low: 0.0 to 0.8 V, input impedance:
3 kΩ) +V Analog input power supply +10.5 V (max allowable current 20 mA) A1 Multi-function analog input 1 0 to +10 Vdc (20 kΩ) resolution 1/1000 0/4 to 20 mA (250 Ω) resolution: 1/500 (A2 only) A2 Multi-function analog input 2 AC Frequency reference common 0 V Safe Disable Inputs HC Safe Disable Input common +24 V (max 10 mA allowed) H1 Safe Disable Input 1 One or both open: Drive output disabled (time from input open to drive output switch off is less than 1 ms) Both Closed: Normal operation H2 Safe Disable Input 2 Multi- Function Relay Output MA N.O. (fault) Digital relay output 30 Vdc, 10 mA to 1 A 250 Vac, 10 mA to 1 A MB N.C.
output (fault) MC Digital output common Multi- Function PHC Output P1 Photocoupler output 1 Digital photocoupler output 48 Vdc, 0 to 50 mA P2 Photocoupler output 2 PC Photocoupler output common Monitor Output MP Pulse train output 32 kHz (max) AM Analog monitor output 0 to 10 Vdc (2 mA or less), Resolution: 1/1000 (10 Bit) AC Monitor common 0 V MEMO- BUS/ Commu- nication R+ Communications input (+) MEMOBUS/Modbus communication.: RS-485 or RS-422, 115.2 kBps (max) R– Communications input (–) S+ Communications output (+) S- Communications output (–)