Chapter 3 PLC System Configuration & Settings - Ignore Version Check if Possible: Even if the version in the backup file is different from the one on the list, the system still tries to restore the parameters. - Ignore Voltage Parameter Check if Possible: Even if the voltage parameter in the backup file is different from the one on the list, the system still tries to restore the parameters. - Ignore Power Section Parameter Check if Possible: Even if the power parameter in the backup file is different from the one on the list, the system still tries to restore the parameters. Note: If the target device does NOT support the partial compatibility, the restoration may not begin.
Before restoration begins, you need to check which condition is supported by the target device by referring to the target device manual. * Full Compatible: All the conditions should be met before the restoration begin. * Force Write: Ignore any difference between the backup file and the device on the list and force the system to restore the parameters. Besides using ISPsoftand EIP Builder, or other PLC editing software, such as HMI or SCADA, you need to use SR devices to appoint which inverter needs to be restored. Refer to the table below. After you have set the configurations, the PLC executes the restorations according to your settings, when the PLC is Power-On or from Stop to Run.
3-113 SR Function Description Retain SR1600 Parameter restoration code 0: Disable (default) 1: When PLC is Power-ON or StopRun, execute the restoration. Once the restoration is complete, clear the ability Yes SR1601.0~SR1601.15 Target device number SR1601.0: refer to target device #1 SR1601.1: refer to target device #2 ︙ SR1601.15: refer to target device #16 Off:Disable (default) On:Execute the restoration on the appointed target device Yes