Delta ISPSoft — 3.3.6.1 Data Exchange Setup - COM1/COM2 /COM

Chapter 3 PLC System Configuration & Settings 3.3.6.1 Data Exchange Setup - COM1/COM2 /COM On the page of tab Data Exchange Setup - COM1 , Data Exchange Setup - COM2 , or Data Exchange Setup - COM , double click a data exchange table which is to be set to open Item window as below. Select the checkbox of Enable to enable the data exchange table in the mode mentioned above. Remote Address is the address of the target slave for data exchange. The Shortest Update Cycle is the period for data exchange of the data exchange table. If the target device does not make any response within the time specified by Connection Timeout , that is timeout.

The master can complete the read and write in a command to improve the efficiency of data exchange by selecting Support Read/write synchronization (Function code 0x17) in which the specific MODBUS function code is used. Please make sure that all devices in data exchange support MODBUS function code for read and write synchronization. Otherwise, the read and write will fail on account of the failure to identify the function codes after the command from the master is received. Remote Device Type is the model of the target slave including Delta PLC and standard MODBUS devices.

3-191 Name Description Item The number of the block for data exchange Enable To select whether to enable the data exchange table when the data exchange is performed. Remote Station Address The slave station address of the data exchange table, One address can be set for multiple data exchange tables. It is a station address for COM1 and COM2 tabs and IP address for Ethernet tab. Local Address The device address range used by the master in the data exchange table > 「 >」:

Output; the data block where the master write to a slave Remote Address The device address range used by a slave in the data exchange table The device range will be in hexadecimal display, if the slave in the data exchange table is a user-defined MODBUS Device. Quantity The size of the data exchange table, which is basically consistent with the result calculated from the device range.