B.2 Parameter Table Default setting value is dependent on parameter o2-04, Drive Model Selection. Parameter can be changed during run. u U: Monitors Monitor parameters allow the user to view drive status, fault information, and other information about drive operation. Parameter List B SIEP C710606 33A OYMC AC Drive – J1000 User Manual 181 No. Name Description Range Def. Mode Addr. Hex Pg. o4: Maintenance Period Use o4 parameters to perform maintenance. o4-01 Accumulated Operation Time Setting Sets the value for the cumulative operation time of the drive in units of 10 h.
0 to 9999 0 O 50B 114 o4-02 Accumulated Operation Time Selection Determines, how the cumulative operation time (U4-01) is counted. 0: Logs power-on time 1: Logs operation time when the drive output is active (output operation time). 0, 1 0 O 50C 114 o4-03 Cooling Fan Operation Time Setting Sets the value of the fan operation time in units of 10 h. 0 to 9999 0 O 50E 114 o4-05 Capacitor Maintenance Setting Sets the value of the capacitor maintenance time monitor U4-05. 0 to 150 0% O 51D 114 o4-07 Soft Charge Bypass Relay Maintenance Setting Sets the value of the Soft Charge Bypass Relay Maintenance monitor U4-06.
0 to 150 0% O 523 114 o4-09 IGBT Maintenance Setting Sets the value of the IGBT Maintenance monitor U4-07. 0 to 150 0% O 525 114 o4-11 U2 Initialize Selection Selects if U2- (Fault History) monitors are reset at drive initialization. 0: Saves the fault monitor data 1: Resets the fault monitor data 0, 1 0 O 510 115 No. Name Description Analog Output Level Unit Mode Addr. Hex U1: Operation Status Monitors Use U1 monitors to display the operation status of the drive. U1-01 Frequency Reference Monitors the frequency 10 V: Max frequency 0.01 Hz O 40 U1-02 Output Frequency Displays the output frequency. Display units are determined by o1-03. 10 V:
Max frequency 0.01 Hz O 41 U1-03 Output Current Displays the output current. 10 V: Drive rated current 0.01A O 42 U1-06 Output Voltage Reference Displays the output voltage. 10 V: 200 Vrms (400 Vrms) 0.1 V O 45 U1-07 DC Bus Voltage Displays the DC bus voltage. 10 V: 400 V (800 V) 1 V O 46 U1-10 Input Terminal Status Displays the input terminal status. Digital input terminal S1 enabled Digital input terminal S2 enabled Digital input terminal S3 enabled Digital input terminal S4 enabled Digital input terminal S5 enabled No output signal available – O 49 U1-11 Output Terminal Status Displays the output terminal statu s.
Multi-Function Digital Output (fault) (terminal MA/MB-MC) No output signal available – O 4A U1-13 Terminal Input Level Displays analog input A1 level: 100% when input is 10 V or 20 mA. 10 V/20 mA: 100% 0.1% O 4E