omron — U: Monitors

B.2 Parameter Table 182 SIEP C710606 33A OYMC AC Drive – J1000 User Manual No. Name Description Analog Output Level Unit Mode Addr. Hex U1-19 MEMOBUS/ Modbus Error Code Displays the contents of a MEMOBUS/Modbus error. CRC Error Data Length Error Not Used Parity Error Overrun Error Framing Error Timed Out Not Used No output signal available – O 66 U1-25 Software No. (ROM) ROM ID No signal output avail. – O 4D U1-26 Software No. (Flash) Flash ID No signal output avail. – O 5B U2: Fault History Use U2 monitor parameters to view fault history data. U2-01 Current Fault Display of the current fault. No signal output avail. – O 80 U2-02 Previous Fault Display of the previous fault.

o4-11 resets the values for U2-02 No signal output avail. – O 81 U4: Maintenance Monitors Use U4 parameters to display drive maintenance information. U4-01 Accumulated Operation Time Displays the cumulative operation time of the drive. The value for the cumulative operation time counter can be reset in parameter o4-01. Use parameter o4-02 to determine if the operation time should start as soon as the power is switched on or only while the run command is present. The maximum number displayed is 99999, after which the value is reset to 0. No signal output avail. 1 h O 4C U4-04 Cooling Fan Maintenance Displays main cooling fan usage time in as a percentage of their expected performance life.

Parameter o4-03 can be used to reset this monitor. No signal output avail. 1% O 7E U4-05 Capacitor Maintenance Displays main circuit capacitor usage time in as a percentage of their expected performance life. Parameter o4-05 can be used to reset this monitor. No signal output avail. 1% O 7C U4-06 Soft Charge Bypass Relay Maintenance Displays the soft charge bypass relay maintenance time as a percentage of the estimated product life. Parameter o4-07 can be used to reset this monitor. No signal output avail. 1% O 7D6 U4-07 IGBT Maintenance Displays IGBT usage time as a percent of expected performance life. Parameter o4-09 can be used to reset this monitor. No signal output avail.

1% O 7D7 U4-08 Heatsink Temperature Displays the heatsink temperature. 10 V: 100 °C 1 °C O 68 U4-09 LED Check Lights all segments of the LED to verify that the display is working properly. No signal output avail. – O 3C U4-13 Peak Hold Current Displays the peak hold current during run. 10 V: Motor rated current 0.01A O 7CF