omron — Defaults by Drive Capacity (o2-04) and ND/HD (C6-01)

B.3 Defaults by Drive Capacity (o2-04) and ND/HD (C6-01) B.3 Defaults by Drive Capacity (o2-04) and ND/HD (C6-01) Table B.1 Single-Phase, 200 V Class Drives Default Settings by Drive Capacity and ND/HD Settings Table B.2 Three-Phase, 200 V Class Drives Default Settings by Drive Capacity and ND/HD Setting Parameter List B SIEP C710606 33A OYMC AC Drive – J1000 User Manual 183 No.

Description Unit Default Settings − Model JZA − B0P1 B0P2 B0P4 C6-01 Normal/Heavy Duty − HD ND HD ND HD ND o2-04 Drive Model Selection Hex 30 31 32 − Motor rated power kW 0.1 0.2 0.2 0.4 0.4 0.75 C6-02 Carrier frequency − 4 7 4 7 4 7 E2-01 Motor rated current A 0.60 1.10 1.10 1.90 1.90 3.30 E2-02 Motor rated slip Hz 2.50 2.60 2.60 2.90 2.90 2.50 E2-03 Motor no-load current A 0.40 0.80 0.80 1.20 1.20 1.80 E2-05 Motor line-to-line resistance Ω 35.98 20.56 20.56 9.842 9.842 5.156 − Momentary power loss ride-through time s 0.1 0.1 0.1 0.1 0.1 0.1 − Mom. power loss Baseblock time s 0.2 0.2 0.2 0.2 0.2 0.3 No.

Description Unit Default Settings − Model JZA − B0P7 B1P5 C6-01 Normal/Heavy Duty − HD HD ND o2-04 Drive Model Selection Hex 33 34 C6-02 Carrier frequency − 4 7 3 7 E2-01 Motor rated current A 3.30 6.20 6.20 8.50 E2-02 Motor rated slip Hz 2.50 2.60 2.60 2.90 E2-03 Motor no-load current A 1.80 2.80 2.80 3.00 E2-05 Motor line-to-line resistance Ω 5.156 1.997 1.997 1.601 − Momentary power loss ride-through time s 0.2 0.2 0.3 0.3 − Momentary power loss Baseblock time s 0.3 0.4 0.4 0.5 No.

Description Unit Default Settings − Model JZA − 20P1 20P2 20P4 20P7 21P5 C6-01 Normal/Heavy Duty − HD ND HD ND HD ND HD ND HD ND o2-04 Drive Model Selection Hex 60 61 62 63 65 − Motor rated power kW 0.1 0.2 0.2 0.4 0.4 0.75 0.75 1.1 1.5 2.2 C6-02 Carrier frequency − 4 7 4 7 4 7 4 7 3 7 E2-01 Motor rated current A 0.60 1.10 1.10 1.90 1.90 3.30 3.30 4.90 6.20 8.50 E2-02 Motor rated slip Hz 2.50 2.60 2.60 2.90 2.90 2.50 2.50 2.60 2.60 2.90 E2-03 Motor no-load current A 0.40 0.80 0.80 1.20 1.20 1.80 1.80 2.30 2.80 3.00 E2-05 Motor line-to-line resistance Ω 35.98 20.56 20.56 9.842 9.842 5.156 5.156 3.577 1.997 1.601 − Momentary power loss ride- through time s 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.3 0.3 − Momentary power loss Baseblock time s 0.2 0.2 0.2 0.2 0.2 0.3 0.3 0.4 0.4 0.5 No.

Description Unit Default Settings − Model JZA − 22P2 24P0 C6-01 Normal/Heavy Duty − HD ND HD ND o2-04 Drive Model Selection Hex 66 68 − Motor rated power kW 2.2 3.0 3.7 5.5 C6-02 Carrier frequency − 3 7 3 7 E2-01 Motor rated current A 8.50 11.40 14.0 19.60 E2-02 Motor rated slip Hz 2.90 2.70 2.73 1.50 E2-03 Motor no-load current A 3.00 3.70 4.50 5.10 E2-05 Motor line-to-line resistance Ω 1.601 1.034 0.771 0.399 − Momentary power loss ride-through time s 0.5 0.5 1 1 − Momentary power loss Baseblock time s 0.5 0.5 0.6 0.7