omron — Monitor Data

C.10 MEMOBUS/Modbus Data Table u Monitor Data Monitor data can be read only. 200 SIEP C710606 33A OYMC AC Drive – J1000 User Manual Register No. Contents 0020H Drive Status 1 bit 0 During Run bit 1 During Reverse bit 2 Drive Ready bit 3 Fault bit 4 Data Setting Error bit 5 Multi-Function Contact Output (terminal MA/MB-MC) bit 6 to bit D Reserved bit E ComRef status bit F ComCtrl status 0021H Fault Contents 1 bit 0 Overcurrent (oC) bit 1 Overvoltage (ov) bit 2 Drive Overload (oL2) bit 3 Overheat 1 (oH1) bit 4 Braking Resistor Overheat (rH) bit 5, 6 Reserved bit 7 EF0 to 5: External Fault bit 8 CPF:

Hardware Fault (includes oFx) bit 9 Motor Overload (oL1), Overtorque Detection 1 (oL3) bit A Reserved bit B Main Circuit Undervoltage (Uv) bit C Undervoltage (Uv1), Soft Charge Circuit Fault (Uv3) bit D Output Phase Loss (LF), Input Phase Loss (PF) bit E MEMOBUS/Modbus Communication Error (CE) bit F Operator Connection Fault (oPr) 0022H Data Link Status bit 0 Writing data or switching motors bit 1 Reserved bit 2 bit 3 Upper or lower limit error bit 4 Data conformity error bit 5 Writing to EEPROM bit 6 to bit F Reserved 0023H Frequency Reference, 0024H Output Frequency, 0025H Output Voltage Reference, 0.1 V units 0026H Output Current 0027H Reserved 0028H Reserved 0029H Fault Contents 2 bit 0, 1 Reserved bit 2 Input Phase Loss (PF) bit 3 Output Phase Loss (LF) bit 4 Braking Resistor Overheat (rH) bit 5 to bit F Reserved 002AH Alarm Contents1 bit 0 to bit 1 Reserved bit 2 Run Command Input Error (EF) bit 3 Drive Baseblock (bb) bit 4 Overtorque Detection 1 (oL3) bit 5 Heatsink Overheat (oH) bit 6 Overvoltage (ov) bit 7 Undervoltage (Uv) bit 8 Reserved bit 9 MEMOBUS/Modbus Communication Error (CE) bit A to F Reserved