omron — EMC Guidelines Compliance

D.2 European Standards Table D.3 EN 61800-3 Category C1 Filters W H LINE L LOAD Figure D.6 EMC Filter Dimensions n DC Reactors for EN 61000-3-2 Compliance Table D.4 DC Reactors for Harmonics Reduction 216 SIEP C710606 33A OYMC AC Drive – J1000 User Manual Drive JZA Filter Data (Manufacturer: Schaffner) Type Rated Current (A) Weight (kg) Dimensions [W x L x H] (mm) Y x X Drive Mounting Screw A Filter Mounting Screw 44P0 A1000–FIV3020–SE 15 0.9 144 x 174 x 50 120 x 161 M4 M5 Drive VZA Filter Data (Manufacturer:

Rasmi) Type Rated Current (A) Weight (kg) Dimensions [W x L x H] Y x X Drive Mounting Screw A Filter Mounting Screw 200 V Single-Phase Units B0P1 A1000–FIV1010–RE 10 0.6 71 x 169 x 45 51 x 156 M4 M5 B0P2 A1000–FIV1010–RE 10 0.6 71 x 169 x 45 51 x 156 M4 M5 B0P4 A1000–FIV1010–RE 10 0.6 71 x 169 x 45 51 x 156 M4 M5 B0P7 A1000–FIV1020–RE 20 1.0 111 x 169 x 50 91 x 156 M4 M5 B1P5 A1000–FIV1020–RE 20 1.0 111 x 169 x 50 91 x 156 M4 M5 200 V Three-Phase Units 20P1 A1000–FIV2010–RE 10 0.8 82 x 194 x 50 62 x 181 M4 M5 20P2 A1000–FIV2010–RE 10 0.8 82 x 194 x 50 62 x 181 M4 M5 20P4 A1000–FIV2010–RE 10 0.8 82 x 194 x 50 62 x 181 M4 M5 20P7 A1000–FIV2010–RE 10 0.8 82 x 194 x 50 62 x 181 M4 M5 21P5 A1000–FIV2020–RE 16 1.0 111 x 169 x 50 91 x 156 M4 M5 22P2 A1000–FIV2020–RE 16 1.0 111 x 169 x 50 91 x 156 M4 M5 24P0 A1000–FIV2030–RE 26 1.3 144 x 174 x 50 120 x 161 M4 M5 400 V Three-Phase Units 40P2 A1000–FIV3005–RE 5 1.0 111 x 169 x 45 91 x 156 M4 M5 40P4 A1000–FIV3005–RE 5 1.0 111 x 169 x 45 91 x 156 M4 M5 40P7 A1000–FIV3005–RE 5 1.0 111 x 169 x 45 91 x 156 M4 M5 41P5 A1000–FIV3010–RE 10 1.0 111 x 169 x 45 91 x 156 M4 M5 42P2 A1000–FIV3010–RE 10 1.0 111 x 169 x 45 91 x 156 M4 M5 43P0 A1000–FIV3010–RE 10 1.0 111 x 169 x 45 91 x 156 M4 M5 44P0 A1000–FIV3020–RE 15 1.1 144 x 174 x 50 120 x 161 M4 M5 Y X A PE Drive Model JZA DC Reactor Model Rating 200V Single-Phase Units B0P1 3.5 A 30 mH B0P2 B0P4 6.7 A 25 mH 400 V Three-Phase Units 40P2 3.5 A 3.0 mH