Victron Lynx Smart BMS — 11.5. Lynx Smart BMS related menu structure of the GX device

Lynx Smart BMS 11.5. Lynx Smart BMS related menu structure of the GX device This is an overview of the Lynx Smart BMS related menu structure of the GX device. To see all menu items shown here, Venus OS v2.90 or later is required. Menu item Default value / unit Description and / or possible values Lynx Smart BMS Shows SoC, voltage and current in the device list Switch On Soft switch to manually switch the Lynx Smart BMS to Standby or On mode State Running Possible states:

Initialising, Pre-charging, Running, Shutdown, Standby Error #0 - No error Error state Battery Voltage, current, power Shows current battery monitor data State of charge % State of charge in percent Consumed AmpHours Ah Displays the consumed AH since the battery was last fully charged Time-to-go Days / Hours Displays the estimated time, based on the current load and discharge floor setting Alarms High internal temperature Ok Low cell voltage Ok Low SoC Ok History Deepest discharge Ah The deepest discharge since last history reset Total charge cycles 0 Number of charge cycles since last history reset Number of full discharges 0 A full discharge is accounted for after SoC falls below 5% Cumulative Ah drawn Ah Cumulative Ah drawn since last history reset Minimum voltage V Minimum voltage since last history reset Maximum voltage V Maximum voltage since last history reset Synchronisation count 0 Cumulative number of battery monitor synchronisations Discharged energy kWh Cumulative number of discharged energy since last history reset Charged energy kWh Cumulative number of charged energy since last history reset Clear history Press to clear Clears all history data Diagsnostics Diagnostics Shows last known errors Fuses Distributor A Ok Possible states:

Ok, Fuse blown Distributor B Ok Possible states: Ok, Fuse blown Fuse 1..4 Ok Possible states: Ok, Not used, Blown Fuses 1..4 Ok Possible states: Ok, Not used, Blown IO System switch Enabled Status of the system switch Page 45 Appendix Pin Name Type Function 11 Remote on/off L Pull-down resistor 12 TEMP + Sensor Positive Input for external temperature sensor (1000A only, not supported, future use) 13 TEMP - Sensor Negative Input for external temperature sensor (1000A only, not supported, future use)