Delta — Groupt 2 Operation Method Parameters

Chapter 4 Parameters | Group 2 Operation Method Parameters 4-6 Revision 2016/03, 6ELE, V1.14 Parameter Function Setting Factory Setting Customer 02.00 Source of First Master Frequency Command 0: Digital keypad UP/DOWN keys or Multi- function Inputs UP/DOWN. Last used frequency saved. 1: 0 to +10V from AVI 2: 4 to 20mA from ACI 3: RS-485 (RJ-45) communication 4: Digital keypad potentiometer 1 02.01 Source of First Operation Command 0: Digital keypad 1: External terminals. Keypad STOP/RESET enabled. 2: External terminals. Keypad STOP/RESET disabled. 3: RS-485 (RJ-45) communication. Keypad STOP/RESET enabled. 4: RS-485 (RJ-45) communication. Keypad STOP/RESET disabled. 1 02.02 Stop Method 0:

STOP: ramp to stop; E.F.: coast to stop 1: STOP: coast to stop; E.F.: coast to stop 2: STOP: ramp to stop; E.F.: ramp to stop 3: STOP: coast to stop; E.F.: ramp to stop 4: Simple Positioning Stop; E.F.:coast to stop 0 02.03 PWM Carrier Frequency Selections 2 to 12kHz 8 02.04 Motor Direction Control 0: Enable forward/reverse operation 1: Disable reverse operation 2: Disabled forward operation 0 02.05 The source of Power-On command and Running command modifies the operating control of the VFD 0: Start running when Power is on. 1: Don’t run when Power is on 2: When the source of the command changes, VFD’s operation remains the same. 3:

When the source of the command changes, VFD’s operation follows the new command. 4: The motor drive can start to run at power on or after reset. When the source of command is a 2-wire external terminal, the operating command changes as the external terminal’s status changes. 1 02.06 Loss of ACI Signal (4-20mA) 0: Decelerate to 0 Hz 1: Coast to stop and display “AErr” 2: Continue operation by last frequency command 3: Continue the operation by following the setting at Pr02-11. 1 02.07 Up/Down Mode 0: by UP/DOWN Key 1: Based on accel/decel time 2: Constant speed (Pr.02.08) 3: Pulse input unit (Pr.02.08) 0