omron — 7.4.5. Transferring the Safety Application Data

29 5 The Warning Dialog Box is displayed. Confirm that there is no problem, and click OK. 6 A dialog box is displayed stating "No connection to the safety device". Check the contents and click OK. 7 As shown in the figure on the right, the font color that is used to display the synchronized data changes to the same color as the one used to specify "Synchronized". Check that a message is displayed stating "The Synchronization process successfully finished". Confirm that there is no problem, and click Close. *When the Sysmac Studio project data matches the Safety Controller data, a message is displayed stating "The synchronization process successfully finished".

*If the synchronization fails, check the wiring and repeat from step 1.