omron — Jogging Operation

4-2 Function Mode •You can also select a multi-step speed by turning on/off the multi-step speed terminals (CF1 to CF4) and set the multi-step speed frequency with F001. 4 Functions Jogging Operation This function allows you to determine and fine-tune the motor stop position. •Allocate 06 (JG) to the desired multi-function input.

4-48 Multi-step speed Multi-step speed terminals Reflected speed CF4 CF3 CF2 CF1 0th 0 0 0 0 Reference source according to the A001 setting 1st 1 A021 2nd 1 0 A022 3rd 1 A023 4th 1 0 0 A024 5th 1 A025 6th 1 0 A026 7th 1 A027 8th 1 0 0 0 A028 9th 1 A029 10th 1 0 A030 11th 1 A031 12th 1 0 0 A032 13th 1 A033 14th 1 0 A034 15th 1 A035 Data Symbol Function name Status Description 06 JG Jogging operation ON Operates at the set jogging frequency. OFF Stop Related functions C001 to C005 Required settings A002 = 01, A038 > b082, A038 > 0, A039 Parameter No. Function name Data Default setting Unit A038 Jogging frequency 0.00/Starting frequency to 9.99 6.00 Hz A039 Jogging stop selection 00:

Free-run stop 01: Deceleration stop 02: DC injection braking stop 00 Hz