4-2 Function Mode „ Specifications of the Relay Output Terminals •The relay output terminals are set to the SPDT contact. The following shows their operations. Electrical specifications 4 Functions MB MA MC Inside the Inverter (Factory default) (a) When used as an alarm terminal (b) When used as an output terminal 4-72 Output terminal Resistance load Inductive load MA-MC Max. contact capacity 250 V AC, 2 A 30 V DC, 3 A 250 V AC, 0.2 A 30 V DC, 0.6 A Min. contact capacity 100 V AC, 10 mA 5 V DC, 100 mA MB-MC Max. contact capacity 250 V AC, 1 A 30 V DC, 1 A 250 V AC, 0.2 A 30 V DC, 0.2 A Min.

contact capacity 100 V AC, 10 mA 5 V DC, 100 mA C036 set value Power supply Inverter status Output terminal sta MA-MC MB-M 00 ON Fault Closed Ope Normal Open Clos OFF ⎯ Open Clos 01 ON Fault Open Clos Normal Closed Ope OFF ⎯ Open Clos C036 set value Power supply Output signal Output terminal status MA-MC MB-MC 00 ON ON Closed Open OFF Open Closed OFF ⎯ Open Closed 01 ON ON Open Closed OFF Closed Open OFF ⎯ Open Closed