Appendix-1 Parameter List Appendix * 2nd control is displayed when SET (08) is allocated to one of from C001 to C005. App-5 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Set value Characteristics, Torque boost A041 Torque boost selection 00: Manual torque boost only 01: Automatic (simple) torque boost 00 No - A241 *2nd torque boost selection 00 A042 Manual torque boost voltage 0.0 to 20.0 5.0 Yes % A242 *2nd manual torque boost voltage 0.0 A043 Manual torque boost frequency 0.0 to 50.0 2.5 Yes % A243 *2nd manual torque boost frequency 0.0 A044 V/f characteristics selection 00: Constant torque characteristics (VC) 01:
Reduced torque characteristics (VP 1.7th power) 06: Special reduced torque characteristics (Special VP) 00 No - A244 *2nd V/f characteristics selection 00 A045 Output voltage gain 20. to 100. 100. Yes % A245 *2nd output voltage gain 100. DC injection braking A051 DC injection braking selection 00: Disabled 01: Enabled 02: Frequency control [A052 set value] 00 No ⎯ A052 DC injection braking frequency 0.0 to 60.0 0.5 No Hz A053 DC injection braking delay time 0.0 to 5.0 0.0 No s A054 DC injection braking power 0. to 100. 50 No % A055 DC injection braking time 0.0 to 60.0 0.5 No s A056 DC injection braking method selection 00: Edge operation 01: Level operation 01 No ⎯