omron — Wiring the Control Circuit Terminals and Relay Terminals

2-2 Wiring Wiring Example of the Control Circuit Terminal Block (Sink Logic) 2 Design Frequency meter Frequency arrival signal (27 V DC 50 mA max.) Note 1: When connecting a relay to the multi-function output terminal, install a surge-absorbing diode in parallel with the relay. The output circuit can break down due to surge voltage when the relay is switched on/off. Note 2: Remove the short-circuit bar when the external power supply is used. Note 3: For the signal line, use a twisted shield wire and apply the shield coating as illustrated below. Keep the length to 20 m or less. Perform insulating treatment. Ground connection is not required. Connect to the ground terminal of the Inverter.

Note 4: Keep the wiring away from the power cable of the main circuit and from the wiring on the relay control circuit. (More than 10 cm apart) 2-11 At sink logic (NPN) : External power supply input At source logic (PNP) : Power supply output Note: By factory default, the input logic of the multi-function input terminal circuit is set to the sink logic. command command 2 1 signal reference reference supply RUN RUN input common power speed speed rotation rotation input for Multi-step Multi-step External terminal Reset Reverse Forward Input AM FS FV FI FC S5 S4 S3 S2 S1 SC P S C P24 PC P1