omron — Extended function mode

3-7 Parameter List 3 Operation * 2nd control is displayed when SET (08) is allocated to one of from C001 to C005. 3-27 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Page External frequency adjustment A101 FI start frequency 0.0 to 400.0 0.0 No Hz 4-10 4-25 A102 FI end frequency 0.0 to 400.0 0.0 No Hz 4-10 4-25 A103 FI start ratio 0. to 100. 0. No % 4-10 4-25 A104 FI end ratio 0. to 100. 100. No % 4-10 4-25 A105 FI start selection 00: Use FI start frequency [A101] 01: 0 Hz start 01 No ⎯ 4-10 4-25 Operation frequency A141 Operation frequency input A setting 00: Digital Operator (F001) 01: Digital Operator (FREQ adjuster) 02:

Input FV 03: Input FI 04: RS485 communication 01 No ⎯ 4-26 A142 Operation frequency input B setting 02 No ⎯ 4-26 A143 Operator selection 00: Addition (A + B) 01: Subtraction (A - B) 02: Multiplication (A × B) 00 No ⎯ 4-26 Frequency addition A145 Frequency addition amount 0.0 to 400.0 0.0 Yes Hz 4-26 A146 Frequency addition direction 00: Adds A145 value to output frequency 01: Subtract A145 value from output frequency 00 No ⎯ 4-26 VR adjustment A151 VR start frequency 0.0 to 400.0 0.0 No Hz 4-10 4-27 A152 VR end frequency 0.0 to 400.0 0.0 No Hz 4-10 4-27 A153 VR start ratio 0. to 100. 0. No % 4-10 4-27 A154 VR end ratio 0. to 100. 100. No % 4-10 4-27 A155 VR start selection 00:

Use VR start frequency [A151] 01: 0 Hz start 01 No ⎯ 4-10 4-27