3-7 Parameter List 3 Operation * 2nd control is displayed when SET (08) is allocated to one of from C001 to C005. 3-35 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Page Others C086 AM offset adjustment 0.0 to 10.0 0.0 Yes V 4-35 4-75 C091 Not used Use "00". *Do not change. 00 ⎯ ⎯ ⎯ C101 UP/DWN selection 00: Do not store the frequency data 01: Store the frequency data 00 No ⎯ 4-60 C102 Reset selection 00: Trip reset at power-on 01: Trip reset when the power is OFF 02: Enabled only during trip (Reset when the power is ON.) 00 No ⎯ 4-57 C141 Logic operation function A input 00: RUN (signal during RUN) 01:
FA1 (constant speed arrival signal) 02: FA2 (over set frequency arrival signal) 03: OL (overload warning) 04: OD (excessive PID deviation) 05: AL (alarm output) 06: Dc (disconnection detected) 07: FBV (PID FB status output) 08: NDc (network error) 10: ODc (Do not use.) 43: LOC (light load detection signal) 00 No ⎯ 4-69 C142 Logic operation function B input 01 No ⎯ 4-69 C143 Logic operator selection 00: AND 01: OR 02:
XOR 00 No ⎯ 4-69 C144 Output terminal P1 ON delay 0.0 to 100.0 0.0 No s 4-70 C145 Output terminal P1 OFF delay 0.0 to 100.0 0.0 No s 4-70 C148 Relay output ON delay 0.0 to 100.0 0.0 No s 4-70 C149 Relay output OFF delay 0.0 to 100.0 0.0 No s 4-70 Control parameter H003 Motor capacity selection 200-V class 0.2/0.4/0.75/1.5/2.2/3.7/5.5/7.5 400-V class 0.4/0.75/1.5/2.2/3.7/5.5/7.5 Factory default No kW 4-76 H203 *2nd motor capacity selection Factory default H004 Motor pole number selection 2 4 6 8 4 No Pole 4-76 H204 *2nd motor pole number selection 4 H006 Stabilization parameter 0. to 255. 100 Yes % 4-76 4-76 H206 *2nd stabilization parameter 100 Yes %