4-2 Function Mode 4-2 Function Mode Output Frequency Setting/Monitor 4 •Set the Inverter output frequency. •With the frequency reference set to the Digital Operator ([A001] = 02), you can set the output frequency in F001. For other methods, refer to the [A001] section in "Frequency Reference Selection" (page 4-7). •If a frequency is set in [F001], the same value is automatically set in multi-step speed reference 0 [A020]. To set the 2nd multi-step speed reference, use [A220], or use [F001] with the SET terminal turned on. To set by using the SET terminal, allocate 08 (SET) to the desired multi-function input.
Functions * To switch to the 2nd multi-step speed, allocate 08 (SET) to the multi-function input terminal and then turn it on. Acceleration/Deceleration Time Set an acceleration/deceleration time for the motor. For a slow transition, set a large value, and for a fast transition, set a small one. * To switch to 2nd acceleration/deceleration time 1, allocate 08 (SET) to the multi-function input terminal and then turn it on. 4-5 Parameter No. Function name Data Default setting Unit F001 Output frequency setting/monitor 0.0/Starting frequency to Max. frequency 6.0 Hz A020 Multi-step speed reference 0 * A220 2nd multi-step speed reference 0 Related functions A001, A201, C001 to C005 Parameter No.
Function name Data Default setting Unit F002 Acceleration time 1 0.01 to 3000 10.0 s * F202 2nd acceleration time 1 F003 Deceleration time 1 * F203 2nd deceleration time 1 Related functions A004, A204, C001 to C005