5 Start Up ENGLISH ‹ Power On Before turning on the power supply, • Make sure all wires are connected properly. • Make sure no screws, loose wire ends or tools are left in the drive. • After turning the power on, the drive mode display should appear and no fault or alarm should be displayed. ‹ Reference and Run Source The drive has a LOCAL and a REMOTE mode. The LED in the LO/RE key indicates the drive status. If the drive is operated in the REMOTE mode, make sure that the correct sources for the fre- quency reference and Run command are set in parameters b1-01/02 and that the drive is in the REMOTE mode.
‹ I/O Setup „ Multi-Function Digital Inputs (S1 to S5) The function of each digital input can be assigned in the H1- †† parameters. The default set- ting functions can be seen in the connection diagram on page 11 . „ Multi-Function Digital Output MA-MB-MC (H2-01) The function of the digital output can be assigned in H2-01. The default setting is “Fault” (H2-01=E). The setting value of H2-01 consist of 3 digits, where the middle and right digit set the function and the left digit sets the output characteristics (0: Output as selected; 1: Inverse output). „ Analog Input A1 (H3- †† ) Analog Input A1 can be used to set the frequency reference when parameter b1-01.
Use the H3- †† parameters to adjust the gain and bias for the analog input. Select the input signal level in the parameter H3-01. NOTICE! If the input signal level of input A1 is switched between voltage and current, make sure that DIP switch S1 is in the correct position and parameter H3-01 is set up correctly. I80E-EN J1000 Quick Start Guide 19 Status Description LO/RE LED LOCAL The Run/ Stop command and the frequency reference are entered at the operator keypad. ON REMOTE The Run command source entered in parameter b1-02 and the frequency reference source entered in parameter b1-02 are used. OFF