sinee — 7.1Basic Function Parameter Group of F00 Group

User Manual of EM730 Series Inverter multi-segment group (F08) and simple PLC parameter group. The same physical channel (AI1 or AI2) cannot be selected for the main frequency source A and auxiliary frequency source B; The process PID and simple PLC modules will not be valid until they are selected. Select the final valid frequency setting channel and operation mode. F00.06=0: main frequency source A The final set frequency only depends on the main frequency source A. F00.06=1: auxiliary frequency source B The final set frequency only depends on the auxiliary frequency source B. F00.06=2: main and auxiliary operation results description of the function code F00.08.

The final set frequency depends on the main and auxiliary operation results. Refer to the F00.06=3: switching between the main frequency source A and auxiliary frequency source B The final set frequency is determined by the status of the input function “26: Frequency source switching”: invalid, depending on the main frequency source A; valid, depending on the auxiliary frequency source B. F00.06=4: switching between main frequency source A and main and auxiliary calculation results 156 Function code Function code name Parameter description Unit Default setting Attribute mailing address F00.06 Options of frequency source 0: main frequency source A 1: auxiliary frequency source B 2:

main and auxiliary operation results 3: switching between main frequency source A and auxiliary frequency source B 4: switching between main frequency source A and main and auxiliary operation results 5: switching between auxiliary frequency source B and main and auxiliary operation results 0 〇 0x0006